Numerical

Condensate Recovery Saving

A plant returns 15,000 kg/h condensate at 90°C instead of using make-up water at 30°C. Calculate sensible heat saving using cp=4.187 kJ/kg·K.

Problem

A plant returns 15,000 kg/h condensate at 90°C instead of using make-up water at 30°C. Calculate sensible heat saving using cp=4.187 kJ/kg·K.

Given Data

Write all quantities in consistent SI units before substitution.

Formula and Solution

Saving = 15,000×4.187×(90−30)=3,768,300 kJ/h = 1,046.75 kW, before accounting for other system effects.

Engineering Check

Check units, magnitude and physical meaning. State any simplifying assumptions and avoid mixing mass flow per hour with energy per second.

Practice Variation

Repeat the problem after changing one input by 10% and explain how the answer responds.